ACV Solo 175 Operations Instructions

Browse online or download Operations Instructions for Water heaters & boilers ACV Solo 175. ACV Solo 175 Operating instructions User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 105
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
prestige
Solo 60
Solo 175
Solo 250
Solo 399
Water Boiler
Warranty Registration Card must be filled out by the customer and mailed within thirty (30) days of installa-
tion in order to gain warranty coverage.
When receiving the PRESTIGE Solo unit, any claims for damage or shortage in shipment must be filed
immediately against the transportation company by the consignee.
Leave all documentation received with appliance with owner for future reference.
* I N S T A L L A T I O N A N D M A I N T E N A N C E *
* I N S T A L L A T I O N A N D M A I N T E N A N C E *
M A N U A L
M A N U A L
2011-50 Manual Prestige 60/175/250/399_TriMax_Revised 2
/6/14
If the information in this manual is not followed exactly, a fire or explosion may
result causing property damage, personal injury or death.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of
this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
- Do not try to light any appliance
- Do not touch any electrical switch; do not use any phone in your building.
- Immediately call your gas supplier from a neighbors phone. Follow the gas
suppliers instructions.
- If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency or the
gas supplier.
L
I
S
T
E
D
WARNING
NOTICE
Page view 0
1 2 3 4 5 6 ... 104 105

Summary of Contents

Page 1 - Water Boiler

prestigeSolo 60Solo 175Solo 250Solo 399Water BoilerWarranty Registration Card must be filled out by the customer and mailed within thirty (30) days of

Page 2 - Table of Contents

Pre-Installation ItemsRecommended ClearancesThe PRESTIGE Solo is approved for zeroclearance to combustibles, excluding vent andboiler piping.-

Page 3

94Product SpecificationsGraph 4: Pressure Loss Through Boiler - Grundfos Circulators Note: Minimum allowable flow rate at full input:- 8 gpm SOLO 175-

Page 4

95Product SpecificationsGraph 6: Pressure Loss Through Boiler - Grundfos Circulators Note: Minimum allowable flow rate at full input:- 19 gpm SOLO 399

Page 8

Additional quality water heating equipment availablefrom ACV-Triangle Tube- Exclusive Tank-in-Tank design- Stainless steel construction- Available in

Page 9 - Pre-Installation Items

Combustion Air Venting5SECTION II - Combustion Air andVentingCombustion Air ContaminationIf the PRESTIGE Solo combustion airinlet is located in

Page 10 - BEST PRACTICE

6Combustion Air VentingVentilation and Combustion AirRequirements - Direct VentA Direct Vent appliance utilizes uncontaminat-ed outdoor air (piped dir

Page 11 - Combustion Air Venting

7Combustion Air VentingMethods of Accessing Combustion Air Into ASpace - Category IVIndoor Combustion AirThe methods listed in this section fora

Page 12

8Combustion Air Venting- Not less than the sum of the areas of allvent connectors in the space.Two Permanent Openings Method. Two permanent openings

Page 13 - Fig. 1:

9Combustion Air VentingCombination of Indoor and OutdoorCombustion Air Indoor Openings: Where used, openings con-necting the interior spaces shal

Page 14 - Fig. 4:

10Combustion Air VentingRemoval of an Existing Boiler from aCommon Vent SystemWhen an existing boiler is removed from acommon venting sys

Page 15

11Combustion Air VentingFor direct-vent appliances, mechanical-vent heating appliances or domestic hotwater equipment, where the bottom of th

Page 16

12Unit PreparationsSECTION III - Unit PreparationsHandling InstructionsThe PRESTIGE Solo is generally easier tohandle and maneuver once re

Page 17

13Unit PreparationsPRESTIGE Solo 60/175/250 Stud Walls -Installation 1. Locate the studs in the general area of theboiler placement.2. Place the w

Page 18 - Unit Preparations

Table of ContentsiPRODUCT AND SAFETY INFORMATIONDefinitions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 19

Boiler PipingSECTION IV - Boiler PipingGeneral Piping Requirements- All plumbing must meet or exceed all local,state and national plumbing codes.- Su

Page 20 - SECTION IV - Boiler Piping

15Boiler PipingBoiler Return Connection with Tee Fitting and Boiler Drain Valve(field supplied)Boiler Supply Connection Pressure Relief Valve(

Page 21 - Boiler Piping

Boiler PipingLow Water Cutoff Device- The PRESTIGE Solo is equipped with a fac-tory installed pressure switch type Low WaterCut Off device.- The min

Page 22

Boiler PipingExpansion Tank and Makeup WaterEnsure the expansion tank is properly sized forthe boiler volume (3 gallons [12 L] for thePRESTIGE

Page 23

18Boiler PipingFig. 6: Piping Component LegendSystem Piping - Zone CirculatorsConnect the PRESTIGE Solo to the systempiping as shown in Fig. 9

Page 24

19Boiler PipingFig. 8 : Near Boiler Piping - Closed Type Expansion TankFig. 7: Near Boiler Piping - Diaphragm Expansion TankNote: Pitch horizontal pip

Page 25

20Boiler PipingSystem Piping - Through BoilerIn new or retrofit applications in whichprimary/secondary arrangement is not utilized, thePRESTIGE

Page 26

21Boiler PipingCHZC2ZC1DHWFig. 9: System Piping - Zoning with Zone CirculatorsFig. 10: System Piping - Zoning with Zone ValvesThe boiler system pipin

Page 27

22Boiler PipingFig. 11: System Piping - Multiple Zone Valve with Single System/Boiler CirculatorFig. 12: System Piping - Single Zone System with Sing

Page 28

23Boiler PipingFig. 13: Multiple PRESTIGE Solo Boiler Piping - Primary / Secondary Note: Consult the PRESTIGETriMax Control Supplement forinformatio

Page 29

Table of ContentsiiBackflow Preventer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Boiler System Piping Ap

Page 30 - SECTION V - Installing Vent /

24Installing Vent/Combustion Air & Condensate DrainSECTION V - Installing Vent /Combustion Air & Condensate DrainInstalling Vent and Combustio

Page 31

25Installing Vent/Combustion Air & Condensate DrainThe drain line materials must be anapproved material by the authority hav-ing jurisdicti

Page 32 - SECTION VI - Gas Piping

26Gas PipingSECTION VI - Gas PipingGas Supply Piping ConnectionThe gas supply piping must be installedin accordance to all applicable local,state

Page 33 - Gas Piping

27Gas PipingNATURAL GASPipe Sizing - Natural GasRefer to Table 1 for schedule 40 metallic pipelength and diameter requirements for naturalgas, b

Page 34

28Gas PipingPROPANE GASPipe Sizing - Propane GasThe unit was shipped with a propaneconversion kit which is located on thetop of the unit i

Page 35

29Gas PipingGas ValveInlet GasPressure PortOffset PressureCover ScrewGasketVenturiOrifice(Natural & Propane)Throttle Screw(Red Plastic Sleeve)Fig.

Page 36 - SECTION VII - Internal Wiring

30Internal WiringSECTION VII - Internal WiringELECTRICAL SHOCK HAZARD. Foryour safety, disconnect electrical powersupply to the unit before

Page 37 - Prestige Solo Internal Wiring

31Internal Wiring1 2CH1Thermostat3 4CH2Thermostat5 6OutdoorSensor7 8DHWAquastator Sensor9 10ManualResetLimit11 12AutoResetLimit13 14+ -ModulationSigna

Page 38 - SECTION VIII- External Wiring

32External WiringSECTION VIII- External WiringInstallation ComplianceAll field wiring made during installation mustcomply with:- National Electrical C

Page 39 - External Wiring

33External Wiring3. Connect the DHW circulator to the linevoltage terminal strip on the wiring panelbelow the PRESTIGE control module,

Page 40

iiiTable of ContentsCirculator Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32-33Alarm Wiring . .

Page 41

34External Wiring2. Follow thermostat manufacturer’s instruc-tions for proper installation. Thermostatshould be located on an inside wa

Page 42 - Diverter Valve

35External WiringSystem Sensor WiringAn optional system temperature sensor can beplaced on the central heating loop to controlthe temperature

Page 43

CH (1) PumpDiverter ValveDHWCH36External WiringFig. 20: Multiple Zone Field Wiring Using Zone Valves

Page 44

Diverter ValveCH (1) PumpCHDHW37External WiringFig. 21: Multiple Zone Field Wiring using Zone Circulators

Page 45

38External WiringDiverter ValveCH (1) PumpDHWZC1ZC2CHFig. 23: Prestige Wiring - Zoning with Zone CirculatorsCH (1) PumpDiverter ValveDHWSYSCHFig. 24:

Page 46 - SECTION IX- TriMax Operation

39External WiringDHW AquastatOutdoor SensorZone#2Zone ValveEnd SwitchZone #1Zone ValveEnd Switch120V/15AServiceC21Smart Tank Snap SetCH1T-stat5Low vol

Page 47 - TriMax Navigation

40TriMax OperationSECTION IX- TriMax OperationThe TriMax Boiler Management System is designed to be flexible yet easy to use. TriMax mon-itors and co

Page 48 - TriMax Operation

41TriMax OperationTriMax NavigationNavigation is performed through four arrow buttons UP, DOWN, LEFT, RIGHT with a centerOK button for making selectio

Page 49 - Home Screen

42TriMax Operationabc de f bbb babc de f bbabc deabc de f bbb babc de f bbabc dabc de f bbb babc de f bbabc deabc de f bbb babc de f bbf bg abc dBoil

Page 50 - Status Line Messages

43TriMax OperationThe status line displays the current operating state of the Prestige.See page 44 for a list of all Status Line Messages.The radiator

Page 51 - Main Menu

ivTable of ContentsCleaning of Old Boiler/System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56Cleaning of New Boiler/System

Page 52 - Heating EZ Setup

44TriMax OperationStatus Line MessagesStatus Line Message DescriptionStandby Indicates that the Prestige is ready to respond when a demand is received

Page 53 - Off 78ºF

45TriMax OperationPress OK ButtonThe EZ Setup menu canbe accessed by selectingthis icon.The CH / DHW Operation Menu can be accessed by selecting this

Page 54 - Domestic Hot Water EZ Setup

46TriMax OperationEZ Setup Navigation: Home Screen>Main Menu>EZ SetupThe EZ Setup menus provide a simple way to quickly customize the

Page 55 - Display EZ Setup

47TriMax OperationSelect CH1 Reset Curve Default: Finned Tube BaseboardSelect CH1 Reset Curve prompts the installer to select an outdoor reset curvefo

Page 56 - Boiler Information

48TriMax OperationNavigation: Home Screen>Main Menu>EZ Setup>DHW EZ SetupDomestic Hot Water EZ Setup allows the installer to quickly customiz

Page 57 - Information Items

49TriMax OperationDHW Priority Timeout Default: OffDHW Priority Timeout prompts the installer to enter an optional time limitthat a domestic hot water

Page 58 - Lockout History

50TriMax OperationCH/DHW Operation Heating EnabledNavigation: Home Screen>Main Menu>CH / DHW OperationCH / DHW

Page 59 - Lockout Screen

51TriMax OperationInformation Item DescriptionBoiler StatusDisplays the current operating state of the Prestige. This is the same asthe status line

Page 60 - Manual Reset Hard Lockouts

52TriMax OperationNavigation: Home Screen>Main Menu>Boiler Information>LockoutHistoryLockout History records the last eight lockouts. Ea

Page 61 - Automatic Reset Soft Lockouts

53TriMax OperationPress any ARROW ButtonThe status line now displays the lockoutThe lockout message is displayed at the top of the screenThe lower rig

Page 62 - Start-Up Preparation

vTable of ContentsSECTION XVII - MAINTENANCE PROCEDURESMaintenance ProceduresReported Problems . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 63

54TriMax OperationManual Reset Hard LockoutsCode Lockout Message DescriptionE1 Failed Ignition The burner failed to light after 5 ignition attempts.E2

Page 64

55TriMax OperationAutomatic Reset Soft LockoutsCode Lockout Message DescriptionE7 High Flue Temperature Flue temperature exceeds high limit.E12 Intern

Page 65 - Start-Up Procedures

56Start-Up PreparationSECTION X - Start-Up PreparationRequirements below must be met forwarranty coverage of Prestige heatexchangers. A tho

Page 66

57Start-Up PreparationCheck and Test AntifreezeFor boiler systems containing antifreeze solu-tions, follow the antifreeze manufacturer’sinstruct

Page 67

58Start-Up PreparationCheck Low Water Cut-Off Device- The PRESTIGE Solo is provided with afactory installed LWCO device that mea-sures sy

Page 68

59Start-Up ProceduresSECTION XI - Start-Up ProceduresFinal Checks Before Start-Upc Read page 40 through 55 regarding theoperation of the TriM

Page 69

60Start-Up Proceduresc Check Vent Piping and Combustion AirPiping.Check for gas-tight seal at every con-nection and seam of the ventin

Page 70 - IMPORTANT

61Start-Up Procedurese. Press the LEFT and RIGHT buttons toadjust the firing rate from 1% to 100%.Hold down the LEFT or RIGHT but-ton to rapidly inc

Page 71 - External Modulating Control

62Start-Up Proceduresc Test High Temperature LimitThe high temperature limit can be temporarilylowered from 210ºF [99ºC] to 102ºF [39ºC] fortesting.1.

Page 72 - Factory TriMax Setting

63Start-Up ProceduresWARNINGFOR YOUR SAFETY READ BEFORE LIGHTINGOPERATING INSTRUCTIONS TO TURN OFF GAS TO APPLIANCE1. STOP! Read the safety informati

Page 73 - Check-Out Procedures

Product & Safety Information1Indicates the presence of a hazardoussituation which, if ignored, will result indeath, serious injury or sub

Page 74 - Installation Record

64Outdoor Reset ControlSECTION XII - Outdoor ResetControlThe use of the outdoor reset function isrequired to optimize boiler efficiency

Page 75 - Maintenance Schedules

65External Modulating ControlSECTION XIII - External ModulatingControlThe boiler can directly accept an analog 0-10VDC signal to control the fi

Page 76 - Procedures

66External Modulating ControlFactory TriMax SettingHEATING SETTINGFACTORY DEFAULTEZ SETUP RESETINSTALLER RESETHeating Operation EnabledDemand Switch &

Page 77 - Maintenance Procedures

67Check-Out ProceduresSECTION XIV- Check-Out ProceduresPerform the following check-out proce-dures as outlined and check off items ascompleted. Wh

Page 78

68Installation RecordSECTION XV - Installation Record

Page 79

69Maintenance SchedulesSECTION XVI - Maintenance ScheduleService TechnicianAt least on an annual basis the following main-tenance should be performed

Page 80

70Maintenance ProceduresSECTION XVII- MaintenanceProceduresMaintenance ProceduresThe PRESTIGE Solo should be inspect-ed and serviced annually, pr

Page 81

71Maintenance ProceduresClean Condensate Drain Assembly1. Loosen the retaining nut from the conden-sate drain assembly and disconnect theassemb

Page 82 - Replacement Parts

72Maintenance ProceduresCheck Expansion TankRefer to Section IV - Boiler Piping for rec-ommended location of the expansion tankand air el

Page 83

73Maintenance ProceduresCheck Control WiringInspect all control wiring. Ensure wiring is ingood condition and properly connected.Check Control Set

Page 84

2Product & Safety InformationDo not use this appliance if any part hasbeen under water. Immediately call aqualified service technician to

Page 85

74Maintenance ProceduresCheck Flame SignalThe flame signal can be read from the BoilerInformation screen. It should be a min. 1μ Α−DC.Check the ignito

Page 86

75Maintenance ProceduresThe combustion chamber insulationcontains ceramic fibers, which are clas-sified as a possible human carcinogen.When e

Page 87

76Replacement PartsReplacement parts must be purchased through a local ACV-Triangle Tube distributor.When ordering part please provide the model numbe

Page 88

77Replacement Parts479103425168Fig. 33: PRESTIGE Solo 60 Jacket ComponentsItem Part # Description1 PTJKT10R Rear Panel2 PTJKT08F Front Jacket Panel3

Page 89

78Replacement Parts493425168Fig. 34: PRESTIGE Solo 175/250 Jacket ComponentsItem Part # Description1 PTJKT12R Rear Panel2 PTJKT08F Front Jacket Panel

Page 90

79Replacement Parts434251687Fig.35: PRESTIGE Solo 399 Jacket ComponentsItem Part # Description1 PTJKT13R Rear Panel2 PTJKT09F Front Jacket Panel3 PTR

Page 91

80Replacement Parts984624711035Fig. 36: PRESTIGE Solo 60 Internal ComponentsItem Part # Description1 PTRKIT125 Heat Exchanger Body2 PTADPT07 Vent Outl

Page 92

81Replacement Parts984624713510Fig. 37: PRESTIGE Solo 175/250 Internal ComponentsItem Part # Description1PSRKIT25 Heat Exchanger Body Solo 175PSRKIT2

Page 93

82Replacement Parts483627951410Fig. 38: PRESTIGE Solo 399 Internal ComponentsItem Part # Description1PSRKIT44 Heat Exchanger Body (30 PSI)PTRKIT128 H

Page 94

83725413968Fig. 39: PRESTIGE Solo 60/175/250 Burner ComponentsReplacement PartsItemPart #PRESTIGESolo 60Part #PRESTIGESolo 175-250Description1 PSRKIT0

Page 95

Pre-Installation Items3SECTION I - Pre-Installation ItemsCode ComplianceThis product must be installed in accordance tothe following:- All applicable

Page 96

84Replacement Parts72104139768Fig. 40: PRESTIGE Solo 399 Burner ComponentsItem Part # Description1 PSRKIT37 Combustion Chamber Insulation2 PSRKIT38 Bu

Page 97

8583416527Fig. 41: PRESTIGE Solo Control EnclosureReplacement PartsItem Part # Description1PTRKIT109 Pressure Gauge and Fitting (All except Solo 399)P

Page 98

86Product Specifications35 1/2” [902 mm]15 3/8” [392 mm]8 1/2” [216 mm]9 7/8” [251 mm]2 1/4” [56 mm]3” [76 mm]1 ” NPT Boiler Supply1/2” NPT Gas Connec

Page 99

87Product Specifications35 1/2” [902 mm]17 1/4” [437 mm]12” [305 mm]4 1/4” [108 mm]14 1/2” [368 mm]2 3/4” [70 mm]19 3/4” [502 mm]7 3/8” [186 mm]3/4” N

Page 100 - Product Specifications

88Product Specifications37 1/2” [953 mm]24 3/4” [628mm]20 1/4” [516 mm]18 5/8” [473 mm]13 1/4” [340 mm]9 1/4” [235 mm]3 1/4” [83 mm]1 1/2” NPT Boiler

Page 101

89Product Specifications11 3/8” [289 mm]1 7/8” [48mm]15 5/8” [396 mm]2 1/4” [58mm]12” [306 mm]1” NPT Boiler Return1” NPT Boiler Supply1/2” NPT Gas Con

Page 102

90Product Specifications11 3/8” [288 mm]6 7/8” [176 mm]11 3/8” [288 mm]1 7/8” [51 mm]15 5/8” [396 mm]3/4” NPT Gas Connection1-1/4” NPT Boiler Supply1-

Page 103

91Product Specifications21 1/4” [540 mm]15 3/8” [390 mm]14 3/4” [374 mm]16 3/8” [416 mm]5 7/8” [150 mm]1 1/2” NPT Boiler Supply1 1/2” NPT Boiler Retur

Page 104

92Product SpecificationsOutput Note 4 157,500 94.1% 95.1% Fuel Combustion Efficiency Input Note 4 Output Note 4 Note 5 Thermal Efficiency Net AHRIRa

Page 105

93Product SpecificationsGraph 2: Pressure Loss Through Boiler-Grundfos CirculatorPressure Drop Comparison -Grundfos Note: Minimum allowable flow rate

Comments to this Manuals

No comments